MPM, APM, PPM, & LTI Series Modbus

®

Register Tables

Serial Communication

Page 11

Register

1

Name Access

Limits or

Range

2

Units

Data

Type

3

Function

Code(s)

Comments

Number Address

(hex)

40122

121

(0079)

Units 4

Read Write

Not applicable

None

Byte

03, 04,

06, 16

Represents the Modbus Little Display MSD-3 value. The hex
value represents the allowable ASCII character.

40123

122

(007A)

Units 5

Read Write

Not applicable

None

Byte

03, 04,

06, 16

Represents the Modbus Little Display MSD-4 value. The hex
value represents the allowable ASCII character.

40124

123

(007B)

Units 6

Read Write

Not applicable

None

Byte

03, 04,

06, 16

Represents the Modbus Little Display MSD-5 (which is the
LSD) value. The hex value represents the allowable ASCII
character.

40125

124

(007C)

Display Intensity Read Write

1 to 8

None

Integer

03, 04,

06, 16

8 is the brightest level. Writing out of range data results in level
1 or 8.

40126

125

(007D)

Adjust Value

Read Write

-500 to 500

1/10 of °C or °F

Integer

03, 04,

06, 16

Actually represents -50.0 to +50.0. Offset value is only applied
to temperature inputs. If Adjust is greater than 27.7°C and the
temperature units are switched to °F, it will be set to 50.0 (lower
than -27.7, set to -50.0).

40127

126

(007E)

RTD Total Value Read Write

1 to 10

None

Integer

03, 04,

06, 16

Value represents the number of parallel RTDs connected to the
signal input. Any other value than these results in a setting of 1.

40128

127

(007F)

Lo Gate Setting Read Write

1 to 999

None

Integer

03, 04,

06, 16

Actually represents 0.1 to 99.9 setting.

40129

128

(0080)

High Gate Setting Read Write

20 to 9999

None

Integer

03, 04,

06, 16

Actually represents 2.0 to 999.9 setting.

40130

129

(0081)

Filter Setting

Read Write

0, 2 to 199

or

202 to 250, 900

Unit-less Integer

03, 04,

06, 16

Display filtering. 0 = no filtering. 2 to 199 = old + ((new -
old)/Filter). For pulse input 900 = Hi-Speed, 202 to 250 = Lo-
Speed where the range is 2 to 50.

40131

130

(0082)

Bypass Setting Read Write

2 to 999

Percent of full

scale or °F

Integer

03, 04,

06, 16

Actually represents 0.2 to 99.9. If the input steps greater than
the bypass value, it will be displayed immediately, with no
filtering occurring. The number represents percent of full-scale
for process inputs and °F for temperature inputs. No effect if
filter = 0.

40132

131

(0083)

Serial Address Read Write

1 to 247

None

Integer

03, 04,

06, 16

Changes to this register are saved but don’t take effect until
next meter reset (Modbus command or power-up). Writing out
of range data results in an address of 247.

40133

132

(0084)

Serial Baud Rate Read Write

0 to 6

None

Integer

03, 04,

06, 16

0 = 300, 1 = 600, 2 = 1200, 3 = 2400, 4 = 4800, 5 = 9600, &
6 = 19200. Changes to this register are saved but don’t take
effect until next meter reset (Modbus command or power-up).
Writing out of range data results in a baud rate of 2400.

40134

133

(0085)

Serial Transmit

Delay

Read Write

0 to 199

ms

Integer

03, 04,

06, 16

Transmit delay to minimize collisions on the RS-485 network.

40135

134

(0086)

Serial Parity

Read Write

0 to 3

None

Integer

03, 04,

06, 16

0 = None with 1 stop bit, 1 = None with 2 stop bits, 2 = Odd,
3 = Even. Changes to this register are saved but don’t take
effect until next meter re-initialization (Writing 0xFF00 to 40299
or power-up). Writing out of range data results in a parity setting
of Even.