Mpm, apm, ppm, & lti series modbus, Register tables serial communication – Dwyer PPM User Manual

Page 15

Advertising
background image

MPM, APM, PPM, & LTI Series Modbus

®

Register Tables

Serial Communication

Page 15

Register

1

Name Access

Limits or

Range

2

Units

Data

Type

3

Function

Code(s)

Comments

Number Address

(hex)

40307

306

(0132)

Relay 1

Off Delay

Read Write

0 to 1999

1/10 of Seconds

Integer

03, 04,

06, 16

40308 – 40309

307 – 308

(0133 – 0134)

Relay 1 Sample

Time

Read Write

0 to 59999

1/10 of Seconds Floating point

03, 04,

06, 16

40310

309

(0135)

Relay 2 Mode Read Write

Not applicable

None

Word; bits

03, 04,

06, 16

See Table 4 for operating modes and bit assignments.

40311 – 40312

310 – 311

(0136 – 0137)

Relay 2

Set Point

Read Write -99999 to 999999

User defined

Floating point

03, 04,

06, 16

40313 – 40314

312 – 313

(0138 – 0139)

Relay 2

Reset Point

Read Write -99999 to 999999

User defined

Floating point

03, 04,

06, 16

40315

314

(013A)

Relay 2

On Delay

Read Write

0 to 1999

1/10 of Seconds

Integer

03, 04,

06, 16

40316

315

(013B)

Relay 2

Off Delay

Read Write

0 to 1999

1/10 of Seconds

Integer

03, 04,

06, 16

40317 – 40318

316 – 317

(013C – 013D)

Relay 2 Sample

Time

Read Write

0 to 59999

1/10 of Seconds Floating point

03, 04,

06, 16

40319

318

(013E)

Relay 3 Mode Read Write

Not applicable

None

Word; bits

03, 04,

06, 16

See Table 4 for operating modes and bit assignments.

40320 – 40321

319 – 320

(013F – 0140)

Relay 3

Set Point

Read Write -99999 to 999999

User defined

Floating point

03, 04,

06, 16

40322 – 40323

321 – 322

(0141 – 0142)

Relay 3

Reset Point

Read Write -99999 to 999999

User defined

Floating point

03, 04,

06, 16

40324

323

(0143)

Relay 3

On Delay

Read Write

0 to 1999

1/10 of Seconds

Integer

03, 04,

06, 16

40325

324

(0144)

Relay 3

Off Delay

Read Write

0 to 1999

1/10 of Seconds

Integer

03, 04,

06, 16

40326 – 40327

325 – 326

(0145 – 0146)

Relay 3 Sample

Time

Read Write

0 to 59999

1/10 of Seconds Floating point

03, 04,

06, 16

40328

327

(0147)

Relay 4 Mode Read Write

Not applicable

None

Word; bits

03, 04,

06, 16

See Table 4 for operating modes and bit assignments.

40329 – 40330

328 – 329

(0148 – 0149)

Relay 4

Set Point

Read Write -99999 to 999999

User defined

Floating point

03, 04,

06, 16

40331 – 40332

330 – 331

(014A – 014B)

Relay 4

Reset Point

Read Write -99999 to 999999

User defined

Floating point

03, 04,

06, 16

40333

332

(014C)

Relay 4

On Delay

Read Write

0 to 1999

1/10 of Seconds

Integer

03, 04,

06, 16

40334

333

(014D)

Relay 4

Off Delay

Read Write

0 to 1999

1/10 of Seconds

Integer

03, 04,

06, 16

Advertising
This manual is related to the following products:

MPM, APM