MPM, APM, PPM, & LTI Series Modbus

®

Register Tables

Serial Communication

Page 12

Register

1

Name Access

Limits or

Range

2

Units

Data

Type

3

Function

Code(s)

Comments

Number Address

(hex)

40136

135

(0087)

Serial Byte-to-

Byte Timeout

Read Write

0 to 254

1/100 of Seconds

Integer

03, 04,

06, 16

This is the timeout between bytes of a Modbus frame. Note that
a value less than the minimum value for the present baud rate
cannot be saved. Minimums are: 300 baud = 0.06 sec,
600 = 0.03, 1200 = 0.02 and 0.01 for 2400 to 19200. Changes
to this register are saved but don’t take effect until next meter
reset (Modbus command or power-up). Writing out of range
data results in a timeout of 2.54 seconds.

40137

136

(0088)

Function Mode Read Write

0 to 3

None

Integer

03, 04,

06, 16

0 = Linear, 1 = Square Root, 2 = Exponent, and 3 = Round
Horizontal Tank

40138

137

(0089)

PV/Rate

Number of Points

Read Write

2 to 32

None

Integer

03, 04,

06, 16

This register is only used when register 40137 is set to Linear.

40139

138

(008A)

Exponent

Read Write 10001 to 29999

None

Integer

03, 04,

06, 16

Actually represents 1.0001 to 2.9999.
Set register 40137 = 2

40140 – 40141

139 – 140

(008B – 008C)

Round Horizontal

Tank Diameter

Read Write

0 to 999.999

Inches

Floating point

03, 04,

06, 16

Decimal point is fixed. The unit of measure is inches; the
volume calculation is in US gallons. The display may be re-
scaled to represent the volume in any engineering units.

40142 – 40143

141 – 142

(008D – 008E)

Round Horizontal

Tank Length

Read Write

0 to 999.999

Inches

Floating point

03, 04,

06, 16

40144 – 40145

143 – 144

(008F – 0090)

Cutoff

Read Write

0 to 999999

User defined

Floating point

03, 04,

06, 16

Represents the cutoff value.

40146

145

(0091)

Total Count

Direction

Read Write

Not applicable

None

Bit

03, 04,

06, 16

0 = count up, 1 = count down

40147 – 40148

146 – 147

(0092 – 0093)

Total Count

Preset

Read Write 0 to 999999999

User defined

Floating point

03, 04,

06, 16

Same as 40302 – 40303 Relay 1 set point.

40149

148

(0094)

Grand Total

Count Direction

Read Write

Not applicable

None

Bit

03, 04,

06, 16

0 = count up, 1 = count down

40150 – 40151

149 – 150

(0095 – 0096)

Grand Total

Count Preset

Read Write 0 to 999999999

User defined

Floating point

03, 04,

06, 16

40152

151

(0097)

Programmable

User F1 Setting

Read Write

0 to 39

User defined

Integer

03, 04,

06, 16

See Table 3.

40153

152

(0098)

Programmable

User F2 Setting

Read Write

0 to 39

User defined

Integer

03, 04,

06, 16

See Table 3.

40154

153

(0099)

Programmable

User F3 Setting

Read Write

0 to 39

User defined

Integer

03, 04,

06, 16

See Table 3.

40155

154

(009A)

Programmable

User Digital

Input 1 Setting

Read Write

0 to 43

User defined

Integer

03, 04,

06, 16

See Table 3.