MPM, APM, PPM, & LTI Series Modbus

®

Register Tables

Serial Communication

Page 4

Register

1

Name Access

Limits or

Range

2

Units

Data

Type

3

Function

Code(s)

Comments

Number Address

(hex)

40001 – 40002

0 – 1

(0000 – 0001)

PV/Rate Display

value

Read Only -99999 to 999999

User defined

Floating point

03, 04

Represents the PV/Rate display value including the decimal
point. Under Range = -99999, Over Range = 999999, and
Open = -99999

40003

2

(0002)

Alarm and Relay

status

Read Only

1 = In Alarm

1 = relay

energized

None

Word; Bits

03, 04

Read alarm status and energized/non-energized status of
relays. Alm = Alarm. Rly = Relay.

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

Alm

8

Alm

7

Alm

6

Alm

5

Alm

4

Alm

3

Alm

2

Alm

1

Rly

8

Rly

7

Rly

6

Rly

5

Rly

4

Rly

3

Rly

2

Rly

1

40004

3

(0003)

Digital Inputs and

Outputs status

Read Only

1 = Input selected

1 = Output active

None

Word; Bits

03, 04

Read the state of the digital inputs and outputs.

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

DI

8

DI

7

DI

6

DI

5

DI

4

DI

3

DI

2

DI

1

DO

8

DO

7

DO

6

DO

5

DO

4

DO

3

DO

2

DO

1

40005 – 40006

4 – 5

(0004 – 0005)

Maximum Display

value

Read Only -99999 to 999999

User defined

Floating point

03, 04

Represents the Maximum display value, including the decimal
point, since last power up or Max Value reset.

40007 – 40008

6 – 7

(0006 – 0007)

Minimum Display

value

Read Only -99999 to 999999

User defined

Floating point

03, 04

Represents the Minimum display value, including the decimal
point, since last power up or Min Value reset.

40009 – 40010

8-9

(0008 – 0009)

Total value

Read Only

0 to 999999999

User defined

Floating point

03, 04

Represents the Total value, including the decimal point, since
last Total reset.

40011 – 40012

10 – 11

(000A – 000B)

Grand Total value Read Only

0 to 999999999

User defined

Floating point

03, 04

Represents the Grand Total value, including the decimal point,
since last Grand Total reset.

40013 – 40014

12 – 13

(000C – 000D)

Total overflow

value

Read Only

0 to 999

User defined

Floating point

03, 04

Represents the Total overflow value, since last Total reset.

40015 – 40016

14 – 15

(000E – 000F)

Total non-

overflow value

Read Only

0 to 999999

User defined

Floating point

03, 04

Represents the Total non-overflow value, since last Total reset.

40017 – 40018

16 – 17

(0010 – 0011)

Grand Total

overflow value

Read Only

0 to 999

User defined

Floating point

03, 04

Represents the Grand Total overflow value, since last Grand
Total reset.

40019 – 40020

18 – 19

(0012 – 0013)

Grand Total non-

overflow value

Read Only

0 to 999999

User defined

Floating point

03, 04

Represents the Grand Total non-overflow value, since last
Grand Total reset.

40021

20

(0014)

PV/Rate Display

value

Read Only -99999 to 999999

User defined

Long Hi

03, 04

Represents the PV/Rate display value excluding the decimal
point. Decimal point setting in 40102.

40022

21

(0015)

PV/Rate Display

value

Read Only

User defined

Long Lo

03, 04

Must be read with 40021.

Advertising