MPM, APM, PPM, & LTI Series Modbus

®

Register Tables

Serial Communication

Page 32

Tables

Table 1.

Input configuration (40101)
Valid input configuration settings are dependent on the meter type (i.e. temperature type and unit settings are only valid when the meter
has a temperature input – otherwise the bits are 0’s for both read and write).

Bit(s)

15, 14, 13, 12, 11, 10, 9, 8

7

6, 5, 4

3, 2, 1, 0

Function Input

Setting

Temperature

Unit Setting

Decimal Point Setting

Temperature Type Setting

00000000 Volts

0 °C

000 dddddd (dddd for temperature)

0000 Type J thermocouple

00010001 Current

1 °F

001 ddddd.d (dddd.d for temperature)

0001 Type K thermocouple

00100010 RTD

010 dddd.dd

0010 Type T thermocouple

00100011 Thermocouple

011 ddd.ddd

0011 Type E thermocouple

10000000 Pulse

100 dd.dddd

0100 Type R thermocouple

101 d.ddddd

0101 Type S thermocouple

110 dddd°u
(° symbol temp unit displayed)

0110 Type B thermocouple

111 dddd.du
(temperature unit displayed)

0111 Type N thermocouple

1000 Type C thermocouple

1001 100

 Platinum RTD (385)

1010 100

 Platinum RTD (392)

1011 1000

 Platinum RTD (385)

1100 1000

 Platinum RTD (392)

1101 10

 Copper RTD

1110 120

 Nickel RTD