NORDAC SK 200E Manual

20

BU

0240

GB

4.1.2

Configuration

Changes to individual parameters are usually necessary for operation. (Exceptions: see Section 4.1.3 )
Configuration can be carried out to a limited extent via the DIP switches. Configuration by means of
software parameterisation is necessary for more extensive parameter changes.

NOTE

Mixing of DIP switch configuration and (software) parameterisation should be avoided.


4.1.2.1 Parameterisation

The use of a ParameterBox (SK CSX-3H / SK PAR) or NordCon software is necessary to change the
parameters.

Parameter group

Parameter numbers

Functions

Remarks

P201 … P207,
(P208)

Data on motor rating plate

P220, Function 1

Measure stator resistance

Value is written to P208

alternatively
P200

Motor data list

Selection of a 4-pole standard
motor from a list

Motor data

alternatively
P220, Function 2

Motor identification

Complete measurement of a
connected motor
Prerequisite: motor at least 3
power levels less than the
frequency inverter

Basic parameters P102 … P105

Ramp times and frequency
limits

Control terminals

P400, P420

Analog and digital inputs


NOTE

Prior to commissioning, it should be ensured that the frequency inverter is in its default setting
(P523).

If configuration is carried out at a parameter level, the DIP switches must also be set to the
"OFF" position.