7 Technical Data Frequency Inverter

Function

Specification

Output frequency

0.0 … 400.0Hz

Pulse frequency

3.0 … 16.0kHz, standard setting = 6kHz
Power reduction > 8kHz for 115/230V device, >6kHz for 400V device.

Typical overload capacity

150% for 60s, 200% for 3.5s

Protective measures against

Over-heating of the frequency inverter,
overvoltage and undervoltage

Short-circuit, earthing fault,
overload, idling

Regulation and control

Sensorless current vector control (ISD), linear V/f characteristic curve,
automatic flux adaptation (energy-saving function)

Motor temperature monitoring

I

2

t motor, PTC / Bimetal switch

Digital input

4x, Low 0-5V, High 14-30V, R

i

= 9.5k

Ω, C

i

= 10nF, cycle time = 4ms

Electrical isolation

Control terminals

Control outputs

digital output:

Brake rectifier:

18-30V DC (according to VI 24V), max. 200mA, max. 100k

Ω load

max. 0.5A choke voltage, voltage according to mains

Interfaces

Standard: RS 485 (USS)

RS 232 (Single Slave)
System bus

Option:

Profibus
CANopen
DeviceNet
AS Interface

Efficiency of frequency inverter

approx. 95% according to size

Storage and transport temperature

-25°C … +60/70°C

Operating / ambient temperature

-25°C … +50°C, according to operating mode (Details: see BU0200)

ATEX: -20…+40°C (Details: Section 4.2)

Long-term storage

Connect the FI and the 24V modules to the mains voltage for 60 minutes at
the latest after one year.

Connect the FI and all other modules to be supplied with 24V to the 24V
control voltage for 60 minutes at the latest after one year.

Maintain this cycle throughout the storage period.

Protection class

IP55, optional IP66

Max. mounting altitude above sea level Up to 1000m:

No power reduction

1000...4000m:

1%/ 100m power reduction (up to 2000m overvoltage cat.
3)

2000...4000m:

Only overvoltage category 2 is maintained, external
overvoltage protection at the mains input is necessary

Waiting period between two power-up
cycles

60 sec for all devices in normal operating cycle

Mains/motor/brake
resistance

4mm

2

flexible with wiring sleeves, 6mm

2

with rigid cable

Control unit /System bus 2.5mm

2

, with1.5mm

2

wiring sleeves

Terminal screw
tightening
torque
1.2...1.5Nm

Connection
terminals

RS485 / RS232

1x RJ12 (6-pin)

External 24V supply voltage

18…30V DC, at least 200...800mA according to load