NORD Drivesystems BU0240 User Manual

Page 22

Advertising
background image

NORDAC SK 200E Manual

22

BU

0240

GB

Details of DIP switches 5/4 and 3

Explanation: (values underlined in brackets) = (relevant parameter / source of function), e.g.: Parameter (P420[01])

{curly brackets}

= {Function} e.g.: {01} „Enable Right“

(See also BU0200) → Table behind parameter

(P420), (P400) or (P434))

*

Default

setting

** only if available (Devices without function "Safe Stop")

Explanation: See table above
Note:
The functions of potentiometers P1 and P2 correspond to those of devices without an AS interface (see table above).
With DIP switches 5 and 4 in the OFF position (default setting), the digital inputs are also active. The functions then correspond to those of devices without
an AS interface (table above). In all other DIP switch combinations the functions of the digital inputs are deactivated.

ASi OUT1 and ASi OUT2 loop the signal level (High / Low) of digital inputs 1 and 2.

Applies to devices SK 205E, SK 215E (without AS interface on board)

DIP

Functions as per the list of digital functions (P420)

Functions as per the list of

analog functions (P400)

5 4 3

Dig 1

Dig 2

Dig 3

Dig 4**

Poti 1

Poti 2

off off off

(P420 [01])*
{01}

"Enable R"

(P420 [02])*
{02}

"Enable L"

(P420 [03])*
{04}

"Fixed freq. 1"

=5Hz (P465[01])

(P420 [04])*
{05}

"Fixed freq. 2"

=10Hz (P465[02])

(P400 [01])*
{01}

"F setpoint"

(P400 [02])*
{15}

"Ramp"

off on off

{01}

"Enable R"

{02}

"Enable L"

{26}

"F setpoint"

{12}

"Quit"

{05}

"F max"

{04}

"F min"

on off off

{45}

"3-on"

{49}

"3-off"

{47}

"Freq. +"

{48}

"Freq. -"

{05}

"F max"

{15}

"Ramp"

on on off

{50}

"F Arr Bit0"

=5Hz (P465[01])

{51}

"F Arr Bit1"

=10Hz (P465[02])

{52}

"F Arr Bit2"

=20Hz (P465[03])

{53}

"F Arr Bit3"

=35Hz (P465[04])

{05}

"F max"

{15}

"Ramp"

The functions of the digital inputs are inactive (control via system bus), however, the settings made
in parameters (P420 [01

… 04]) result in the activation of the correspondingly parameterised input,

for the functions designated with ..² in the function list (e.g.: {11}²= "Quick stop).

off off on

(P420 [01])
no function

(P420 [02])
no function

(P420 [03])
{04}

"Fixed freq. 1"

=5Hz (P465[01])

(P420 [04])
{05}

"Fixed freq. 2"

=10Hz (P465[02])

(P400 [01])
{01}

"F setpoint"

(P400 [02])
{15}

"Ramp"

off on on

{14} "Remote control"

"Encoder track A" "Encoder track B"

{01}

"Enable R"

{01}

"F setpoint"

{05}

"F max"

on off on

{14} "Remote control"

{01}

"Enable R"

{10}

"Block"

{66}

"Release brake"

{01}

"F setpoint"

{05}

"F max"

on on on

{14} "Remote control"

{51}

"F Arr Bit1"

=10Hz (P465[02])

{52}

"F Arr Bit2"

=20Hz (P465[03])

{53}

"F Arr Bit3"

=35Hz (P465[04])

{05}

"F max"

{15}

"Ramp"

Applies to devices SK 225E, SK 235E (without AS interface on board)

DIP

Functions as per the list of digital functions (P420)

Functions as per the list of digital outputs

(P434)

5 4 3

ASi

In1

ASi

In2

ASi

In3

ASi

In4

ASi

Out1

ASi

Out2

ASi

Out3

ASi

Out4

off off off

(P480 [01])*
{01}

"Enable R"

(P480 [02])*
{02}

"Enable L"

(P480 [03])*
{04}

"Fixed freq. 1"

=5Hz (P465[01])

(P480 [04])*
{12}

"Quit"

(P481 [01])*
{07}

"Error"

(P481 [02])*
{18}

"Standby"

"DigIn1" "DigIn2"

off on off

{04}

"Fixed freq. 1"

=5Hz (P465[01])

{05}

"Fixed freq. 2"

=10Hz (P465[02])

{06}

"Fixed freq. 3"

=20Hz (P465[03])

{07}

"Fixed freq. 4"

=35Hz (P465[04])

{07}

"Error"

{18}

"Standby"

"DigIn1" "DigIn2"

on off off

{01}

"Enable R"

{02}

"Enable L"

{47}

"Freq. +"

{48}

"Freq. -"

{07}

"Error"

{18}

"Standby"

"DigIn1" "DigIn2"

on on off

{51}

"F Arr B1"

=10Hz (P465[02])

{52}

"F Arr B2"

=20Hz (P465[03])

{53}

"F Arr B3"

=35Hz (P465[04])

{14}

"Remote

control"

{07}

"Error"

{18}

"Standby"

"DigIn1" "DigIn2"

The functions of the digital inputs are inactive (control via system bus), however, the
settings made in parameters (P480 [01

… 04]) result in the activation of the

correspondingly parameterised bits, for the functions designated with ..² in the function
list (e.g.: {11}²= "Quick stop).

off off on

(P480 [01)
no function

(P480 [02])
no function

(P480 [03])
{04}

"Fixed freq. 1"

=5Hz (P465[01])

(P480 [04])
{12}

"Quit"

(P481 [01])
{07}

"Error"

(P481 [02])
{18}

"Standby"

"DigIn1" "DigIn2"

off on on

{14}

"Remote control"

{04}

"Fixed freq. 1"

=5Hz (P465[01])

{05}

"Fixed freq. 2"

=10Hz (P465[02])

{06}

"Fixed freq. 3"

=20Hz (P465[03])

{07}

"Error"

{18}

"Standby"

"DigIn1" "DigIn2"

on off on

{14}

"Remote control"

{01}

"Enable R"

{47}

"Freq. +"

{48}

"Freq. -"

{07}

"Error"

{18}

"Standby"

"DigIn1" "DigIn2"

on on on

{14}

"Remote control"

{50}

"F Arr B0"

=5Hz (P465[01])

{51}

"F Arr B1"

=10Hz (P465[02])

{52}

"F Arr B2"

=20Hz (P465[03])

{07}

"Error"

{18}

"Standby"

"DigIn1" "DigIn2"

Advertising