NORD Drivesystems BU0240 User Manual

Page 34

Advertising
background image

NORDAC SK 200E Manual

34

BU

0240

GB

Parameter list - inverter functions (selection)

Parameter

Description

Factory

setting

Settings / functions (selection)

P102

Start-up time

Start-up time (acceleration ramp) is the
time corresponding to the linear
frequency rise from 0Hz to the set
maximum frequency (P105).

[2.00]

Note: Values < 0.1 must be avoided

P103

Braking time

The braking time (braking ramp) is the
time corresponding to the linear
frequency reduction from the set
maximum frequency (P105) to 0Hz.

[2.00]

Note: Values < 0.1 must be avoided

P104

Minimum
frequency

The minimum frequency is the
frequency supplied by the FI as soon as
it is enabled and no additional setpoint
is set.

[0]

P105

Maximum
frequency

Is the frequency provided by the FI after
it has been enabled and the maximum
setpoint value is available.

[50]

P200

motor list

If a 4-pole NORD motor is used, the
preset motor data can be called up.

[0]

Select appropriate motor power

P201 – P208

Motor data

If a 4-pole NORD motor is not used, the
motor data on the rating plate must be
entered here.

[xxx] Data

according to rating plate

P220

Parameter
identification

The motor data is automatically
determined by the FI with this
parameter.

[0]

01= only stator resistance
02= motor identification

P400

Setpoint input
function

Definition of the functions of the various
setpoint inputs

Input selection:

Poti P1 (P400, Array -01)
Poti P2 (P400, Array -02)
DIN 2 (P400, Array -06)
DIN 3 (P400, Array -07)

[xxx]

00= No function
01= Setpoint frequency
15= Ramp time (only P1 / P2)

P420

Digital input
functions

Definition of the functions of the various
setpoint inputs

Input selection:
DIN 1(P420, Array -01)
DIN 2 (P400, Array -02)
DIN 3 (P400, Array -03)
DIN 4 (P400, Array -04)

[xxx]

00= No function
01= Enable right
02= Enable left
04= Fixed frequency
05= Fixed frequency
26= Analog function (only DIN2/3)

P428

Automatic start

Inverter enable with "Mains On"

[0]

0= Off (enable with flank)
1= On (enable with level)
Note:

one digital input must be

programmed and set to enable.

P465
Fixed frequency /
Fixed frequency
array

Definition of fixed frequency values

Selection:
Fixed frequency 1 (P465, Array -01)
Fixed frequency 2 (P465, Array -02)

[xxx]

P509

Control word
source

Selection of the interface via which the
FI is controlled.

[0]

00= Control terminals or keyboard
01= Only control terminals
03= System bus

P523

Factory setting

Frequency inverter is restored to the
factory setting

[0]

00= No change
01= Load factory setting