3.6 Relay

The PF4 provides a freely configurable internal isolated relay contact.

Normally closed (NC)

 Common

(COM)

Normally open (NO)

The relay can be controlled by freely configurable alarms. The following can also be set:

Time delay

The relay is only switched on when an alarm endures for a certain minimum time.

Switch off when alarm finished

The relay automatically disengages when the alarm is no longer active; otherwise the relay remains

active until it is reset manually.

Maximum duty cycle

The relay stays on for at most the time set and is then switched off.

The relay can only be activated by a measured value. Assignment of more than one measured value is not

possible.

3.7 Service Interface

Using the HW4 software, the service interface (UART) allows device settings, loading of language data and

updating of the firmware. The service interface is located inside the housing. It is connected to the computer

with the HW4 software with an AC3006 or AC3009 connection cable.

Important:

The PF4 can be supplied with power through the service cable. The service cable provides insufficient power

for correct differential power measurement.

For sensor adjustment, the PF4 must be supplied with power from a suitable power source via the terminals

provided (K2-1: -/~, K2-2: +/~).