6.4.4

Scaling of the Analog Input

The analog input can be scaled within the range 0…3.2 V / 0…25 mA. If, for example, only 1...2.5 V are to be

shown in the display due to the application or a connected third-party probe, the analog input must be scaled

accordingly. Figure 16 illustrates scaling of the analog input.

Legend for

 Figure 16

:

Input-Range:

0…3.2 V / 0…25 mA

RangeLo:

0 V / 0 mA (lowest input value)

RangeHi:

3.2 V / 25 mA (highest input value)

ScaleLo:

Bottom scale limit (min. value shown in display)

ScaleHi:

Top scale limit (max. value shown in display)

Figure 16: Graphic representation of scaling the analog input

Example:

An ambient pressure sensor with an analog output of 500…1000 mV (900…1100 hPa) is to be connected and

its signal shown in hPa. The

Input-Range

with the limits

RangeLo

= 500 mV and

RangeHi

= 1000 mV and the

display range Scale with

ScaleLo

= 900 and

ScaleHi

= 1100 mean that an input voltage of 500 mV shows the

value 900 in the display and an input voltage of 1000 mV the value 1100. The unit is configured with the HW4

software as "hPa".

Remark on PF4 with HC2 and analog input:

The formula for calculation of the

Display-Value

is: