E-m-pf4-v1_00 – ROTRONIC PF4 User Manual

Page 38

Advertising
background image

E-M-PF4-V1_00

Rotronic AG

Bassersdorf, Switzerland

Document Code

Unit

PF4 Differential Pressure Transmitter:

Instruction Manual

Instruction Manual

Document Type

Page 38 of 54

Document Title

© 2014; Rotronic AG

E-M-PF4-V1_00

Variant 2: Differential pressure & Pt100 connection

Main Menu

Menu Navigation

(valid for all menus)

Select

Options

(Enter key)

Selection of the menu point

or menu

Return; menu one level up

+

Line up; option right

-

Line down; option left

Device Settings

Select

Options

Units

Unit for the ambient pressure (Pressure):

Metric

, English

Backlight

On

, Off, Key Press

Contrast

0…99 (suitable setting 15…40)

Trend

On

, Off

Pressure

Ambient pressure (suitable setting: 950 - 1050 hPa):

0…9,999 hPa (Units: Metric)

0…9,999 inHg (Units: English)

Value 1

Main display: None, DiffPress, TempPt100

Value 2

Main display: None, DiffPress, TempPt100

Device Information

The device information cannot be changed (except for "Name" and "Address").

"Name" and "Address" can be set with the HW4 software.

Settings for Differential Pressure

Select

Options

Unit

Unit for the differential pressure: Pa, inH

2

0, mpsi, mbar,

mmHg, mmH

2

O, Torr, g/cm2

Filters

Filter value (0 = fast, 13 = very slow): 0…13 (suitable

setting 0…7)

RefValue

Current differential pressure can be changed

<Adjust>

Applies change to RefValue

<Zero Adjust>

Performs a zero adjustment

<Reset Adjustment>

Cancels the last change (<Adjust>, <Zero Adjust>)

Pt100 Adjust (1)