5

Electrical Installation

This section describes the general safety precautions for electric wiring.

5.1.1

Cable Grip and Cable Specifications

The PF4 comes with a M16 cable grip with screw cable gland. The M16 cable grip offers effective sealing if

cables with external diameters of 6 to 7 mm (0.236 to 0.275 inch) with connection wires per 18 AWG are used.

5.1.2

General Connection Information

Heavy machinery and measuring instruments should not share the same electric cables for power supply. If this

cannot be avoided, noise filters and surge protectors should be used, as integrated in most UPS devices.

5.1.3

Signal Cable Information

The following guidelines are derived from the European standard EN 50170 for the transmission of signals by

copper wires. Note on installation planning: when determining the position of machinery and equipment, the

rules given in EN 50170 should be followed with due regard to local circumstances.

All ROTRONIC products are tested for electromagnetic compatibility according to EMC Directive 2004/108/EC

and the following European standards:

-

EN 61000-6-1: 2007, EN 61000-6-2: 2005

-

EN 61000-6-3: 2007, EN 61000-6-4: 2007

Whenever the level of electromagnetic interference is expected to be high, both the devices and signal cables

should be placed as far away as possible from the source of interference.

In general, signal cables should be installed in bundles or channels / conduits, separate from other cables as

indicated in the table below: