E-m-pf4-v1_00, 5 hc2 / analog connection – ROTRONIC PF4 User Manual

Page 19

Advertising
background image

E-M-PF4-V1_00

Rotronic AG

Bassersdorf, Switzerland

Document Code

Unit

PF4 Differential Pressure Transmitter:

Instruction Manual

Instruction Manual

Document Type

Page 19 of 54

Document Title

© 2014; Rotronic AG

E-M-PF4-V1_00

4.5 HC2 / Analog Connection

The PF4 can optionally be ordered with an E2 socket. This interface and its possible uses are described below.

4.5.1

Use of HC2 Probe

The PF4 can optionally be set up for a HC2 probe. After connection of

a HC2 probe, it is possible to measure and display three parameters:

 Differential

pressure

 Humidity

Temperature / Calculation

Figure 8: E2 and differential pressure connection on the bottom side

of the PF4

All HC2 probes currently available can be connected. The measured data of the HC2 probe is evaluated digitally

and shown on the display. Two of the measured values can be assigned to the analog outputs (chapter 6.2 )

and processed further. The optional Ethernet interface (chapter 6.3 ) of the PF4 can output all measured values.

4.5.2

Use of Analog Input

The device menu is used to switch between use of a HC2 probe and an analog third-party probe. The display

of the PF4 switches automatically to the units mA / mV of the analog input.

The input is reconfigured with the device menu:

MENU > Probe Information > Sensor Type

Select between the following options:

HC2

Digital HC2 probes are read out

Analog In

Analog input is used

The PF4 then asks the user to confirm the sensor change and restarts with the corresponding display

configuration.

Remark: