Environmental Monitoring Unit

UltraSCSI RAID Enclosure 3–11

Note

For detailed instructions about using the

set emu

commands, refer to the array controller CLI documentation.

Table 3–2

EMU Set Point Temperature Conversions

°F

°C

°F

°C

°F

°C

°F

°C

°F

°C

32

0

50

10

68

20

86

30

104

40

34

1

52

11

70

21

88

31

106

41

36

2

54

12

72

22

90

32

108

42

37

3

55

13

73

23

91

33

109

43

39

4

57

14

75

24

93

34

111

44

41

5

59

15

77

25

95

35

113

45

43

6

61

16

79

26

97

36

115

46

45

7

63

17

81

27

99

37

117

47

46

8

64

18

82

28

100

38

118

48

48

9

66

19

84

29

102

39

120

49

Table 3–3

Temperature Set Point Rules—EMU Firmware
Versions 1.0 and 1.1

1.

Enter all temperatures in degrees Celsius (°C). Do not use fractions,
decimals, or degrees Fahrenheit (°F).

2.

The EMU set point (sensor_3) temperature must be a minimum of
6°C (11°F) greater than the highest expected ambient (intake)
temperature.

3.

The backplane set points (sensor_1 and sensor_2) must be the same
temperature and a minimum of 13°C (23°F) greater than the highest
expected ambient temperature. This requires a minimum setting of
7°C (13°F) greater than the EMU set point.