HP Array Controller HSG V8.7 Software User Manual
Page 431

LED Codes
C–7
■● ❍ ❍ ● ❍ ●
25
Recursive Bugcheck detected
The same bugcheck has occurred
three times within ten minutes, and
controller operation has
terminated.
Reset the controller. If this fault pattern
is displayed repeatedly, follow the
repair action(s) associated with the Last
Failure code that is repeatedly
terminating controller execution.
■❍ ❍ ❍ ❍ ❍ ❍
0
No program card detected or kill
asserted by other controller
Controller unable to read program
card
Ensure that program card is properly
seated while resetting the controller. If
the error persists, try the card with
another controller; or replace the card.
Otherwise, replace the controller that
reported the error.
❏❍ ❍ ❍ ❍ ❍ ❍
0
Catastrophic controller or power
failure
Check power. If good, reset controller.
If problem persists, reseat controller
module and reset controller. If problem
is still evident, replace controller
module.
Table C–1
Solid OCP Patterns (Continued)
Pattern
OCP
Code
Error
Repair Action