6

Communication Settings for RS-485/RS-232 communication interface:

Baud rate:

------------

9600 baud

Stop bit:

------------

1

Data bits:

------------

8

Parity:

------------

None

Flow Control: ------------

None

RS-485 communication interface connection:

The RS485 converter/adapter must be configured for: multidrop, 2 wire, half duplex
mode. The transmitter circuit must be enabled by TD or RTS (depending on which
is available on the converter/adapter). Settings for the receiver circuit should follow
the selection made for the transmitter circuit in order to eliminate echo.

Pin D ------------ RS-485 T(-) or R(-)
Pin E ------------ RS-485 T(+) or R(+)
Pin B ------------ RS-485 GND (if available)

RS-232 communication interface connection:

Crossover connection has to be established:

Pin D ------------ RS-232 RX (pin 2 on the DB9 connector)
Pin E ------------ RS-232 TX (pin 3 on the DB9 connector)
Pin B ------------ RS-232 SIGNAL GND

(pin 5 on the DB9 connector)