COMMAND

NAME

DESCRIPTION

NO.

COMMAND SYNT

A

X

COMMAND

ARGUMENT 1

ARGUMENT 2

ARGUMENT 3

ARGUMENT 4

RESPONSE

Flow

Requests the current flow

sensor reading in current EU

1

F

<V

alue> (Actual flow in

current engineering units)

Te

mperature

**

Requests the current

temperature reading in current

EU (

°C or

°F)

2

T

<V

alue> (Actual temp. in

current engineering units)

DIagnostic

Events

Read/Reset current status of

Diagnostic Events Log register

.

3

DE

NO ARGUMENT

(read status)

DE:0x10

0x10 – diagnostic word

(16 bits wide)

R (reset Event

Log register to

0x00)

DE:0x0

Diagnostic

Mask

Display/Set Diagnostic Events

Mask register

See list of the Diagnostic

Events below

.

4

DM

NO ARGUMENT

(read current

Diagnostic Events

Mask register)

DM:0x9FFF

0x9FFF – diagnostic mask

(16 bits wide).

Set bit - Enable

Clear bit - Disable

<V

alue>

0x0000

To

0xFFFF

NOTE: all 6

characters are

required

DM:0x9FFF