Section 1. Installation

TABLE 1.2-1. CR9000X Battery and Charging Circuitry Specifications

CR9000X WITH STANDARD BATTERIES (4):
Battery life, no supplemental
charge

13 hours to 10.5 V (assuming 1A current)

Voltage at full discharge

10.5 volts

Recharge time
(AC Adapter input)

9 hours from 100% discharge

5 hours from 50% discharge.

Individual Batteries
Type Yuasa

NP7-6

Nominal Voltage

6 Volts

Nominal Capacity

20 hr rate of 350 mA to 5.25 V, 7 Ahr

10 hr rate of 650 mA to 5.25 V, 6.5 Ahr

Operating Temperature range:

Charge

–15 to 50 ºC

Discharge

–20 to 60 ºC

Shelf Life @ 20 ºC:

1 month

97%

3 months

91%

6 months

85%

Life Expectancy:

Standby

3 to 5 years

Cycle use

100% depth of discharge

250 cycles

50% depth of discharge

550 cycles

30% depth of discharge

1200 cycles

Number of batteries

4

CHARGING CIRCUIT

Type

Controlled voltage with temperature
compensated voltage regulation

Charging Current

limited to 2 Amps max

POWER SUPPLY TRANSFORMER
Input Voltage

100-240 VAC,
50-60 Hz

Input Current

1.4 A maximum

Output Voltage

17.5 VDC

Output Current

3.5 A maximum

At typical CR9000X current demand, the batteries are 100%
discharged at a system battery voltage of 10.5 V. Discharging
the batteries below this voltage damages the cells.
As can be
seen from the above table, battery life expectancy decreases with
depth of discharge.

NOTE

CSI'S WARRANTY DOES NOT COVER BATTERIES

.

Avoid deep discharge states by measuring and monitoring the battery voltage
(BattVolt instruction) as part of the collected data and periodically checking
the voltage record to be sure the batteries and charging system are working
correctly.