8.1.1 Configuring the NL200/201

Connect to the NL200/201 in DevConfig (see Section 6, Configuring the

NL200/201).

On the NL200 tab:

o Set Bridge Mode to disable.

o Set Use DHCP to disable.

o Input the IP Address, Network Mask, and Default Gateway. These

values can be provided by your network administrator.

On the Network Services tab:

o Make note of the PakBus/TCP Server Port.

8.1.2 Configuring the Datalogger

The datalogger must first be configured for internet

communication (i.e., through an NL115, an NL120, a second

NL200/201, or a cellular modem).

Connect a serial cable from the PC COM port to the datalogger’s RS-232

port.

Open DevConfig. Select the device type of the datalogger (CR800,

CR1000, or CR3000), the appropriate

Communication Port, and Baud

Rate. Press Connect to connect to the datalogger.

On the Network Services tab:

o Under PakBus TCP Client Connections, input the NL200/201’s IP

address and PakBus TCP Server Port.

Press

Apply to save the changes and then close DevConfig.

9. Troubleshooting

This section covers some common problems that might be encountered when

using the NL200/201. This is not comprehensive but should provide some

insight and ability to correct simple errors without a call to Campbell Scientific

technical support.

When your Campbell Scientific software cannot establish a link to a remote

datalogger that is connected to the NL200/201, do the following:

1. Check all your power connections.

Your NL200/201 and any hub and/or router being used must be

connected to power. Check power indicator lights to make sure your

devices are powered.