Campbell Scientific NL200/NL201 Network Link Interface User Manual

Page 49

Advertising
background image

Appendix C. NL200/201 Settings

connection with the remote server and if the connection fails to open, the

device will continue to retry at an interval of 60 seconds. If data arrives on

the RS-232 port when no TCP connection exists, the device will buffer up

the data (up to 1500 bytes) and immediately attempt to open a connection

to deliver the data. If the remote server closes the connection due to error,

the device will make a best effort to save any data that was in process and

re-queue it to be sent on the next successfully-opened TCP connection.

PakBus

This port uses the PakBus® protocol.

Modbus/TCP Gateway

The device will listen for incoming MODBUS/TCP connections from a

remote client. The port number of the listening connection is specified in

the “RS-232 Service Port Number” setting. The device will convert

incoming MODBUS/TCP frames to MODBUS/RTU and forward them to

the RS-232 port. The device will wait for a response from the

MODBUS/RTU device and forward the response back to the remote

MODBUS/TCP client over the established TCP connection.

Disabled

This port will not be used.

RS-232 Service Port Number

This setting is used when the RS-232 port is configured as a Serial Server or

MODBUS/TCP gateway. To communicate with a TCP/IP server, the client

application must open a socket to that server. The socket of a specific server is

uniquely identified by an IP address of the host where the server is running and

a port number associated with the server application on that host. This entry is

where the port number of the server is set. Ensure that the client application is

set to use the same port number as configured here. Most MODBUS/TCP

applications use port 502. (range 1..65535)

RS-232 Baud Rate

This setting specifies the baud rate of the RS-232 port. The connected device

must be set to communicate at the same baud rate.

RS-232 RTS

The NL200/201 asserts the RTS and DTR lines when doing RS-232

communications. This setting allows the user to disable the RTS line if needed

so that it will not be asserted. Some hardware will not function if the RTS line is

asserted, but typically, it is not necessary to change this setting from its default

(enabled).

RS-232 TCP Timeout

This setting will determine how fast the device will timeout on the open TCP

connection. For Serial Server and MODBUS/gateway configurations the

device will close the TCP connection if no activity is detected for the timeout

period. For the TCP Client configuration the device will close the TCP client

connection if no activity is detected and then immediately open another

connection with the remote server. This behavior helps to ensure that the

C-5