Appendix C. NL200/201 Settings

connection is functional as the device does not know the frequency or nature of

the expected data. Set to 0 for no timeout (not recommended). (range 0..999)

(seconds)

RS-232 PakBus Beacon Interval

This setting, in units of seconds, governs the rate at which the NL200/201 will

broadcast PakBus® messages on the associated port in order to discover any

new PakBus neighboring nodes. It will also govern the default verification

interval if the value of the Verify Interval setting for the associated port is zero.

RS-232 PakBus Verify Interval

This setting specifies the interval, in units of seconds, that will be reported as

the link verification interval in the PakBus® hello-transaction messages. It

will indirectly govern the rate at which the NL200/201 will attempt to start a

hello transaction with a neighbor if no other communication has taken place

within the interval.

Neighbors Allowed RS-232

Example: (129,129) (1084,1084)

In the example above, nodes 129 and 1084 are assigned as neighbors to the

NL200/201.

This setting specifies, for a given port, the explicit list of PakBus® node

addresses that the NL200/201 will accept as neighbors. If the list is empty (the

default value), any node will be accepted as a neighbor. This setting will not

affect the acceptance of a neighbor if that neighbor’s address is greater than

3999. The formal syntax for this setting follows:

neighbor := { "(" range-begin "," range-end ")" }.

range-begin := pakbus-address. ;

range-end := pakbus-address.

pakbus-address := number. ; 0 < number < 4000

RS-232 Modbus Timeout

This setting determines how long the MODBUS/TCP to MODBUS/RTU

gateway will wait for an answer from the MODBUS slave device(s) attached to

the RS-232 port. If no answer is received within the timeout period, the

MODBUS/TCP server will reply to the MODBUS/TCP client with error code

0x0B(Target Device Failed to Respond). (milliseconds)

RS-232 TCP Serial Client IP Address

This setting specifies the IP address of the outgoing TCP Serial client

connection that the device should maintain. If the connection fails, the device

will retry until the connection succeeds. No entry specifies that no client

connection will be made.