SECTION 4 - CONTROL COMPONENTS

4-16

– JLG Lift –

3121231

2

Ancillary 1 Anti-Tie-down

0

0-1

2

Ancillary 2 Anti-Tie-down

0

0-1

2

Mode Select Delay (active before time-out)

5 Sec.

0 - 60 Seconds

2

Invert Lift Direction

NO

YES/NO

2

Lift Lock Delay

5 Sec.

0 - 60 Seconds

2

Acceleration (platform lowered)

80

1 - 100

2

Deceleration (platform lowered)

80

1 - 100

2

Turn Acceleration (platform lowered)

50

1 - 100

2

Turn Deceleration (platform lowered)

50

1 - 100

2

Maximum Forward Speed (platform lowered)

100

1 - 100

2

Minimum Forward Speed (platform lowered)

40

1 - 100

2

Maximum Reverse Speed (platform lowered)

50

1 - 100

2

Minimum Reverse Speed (platform lowered)

20

1 - 100

2

Maximum Turn Speed (platform lowered)

20

1 - 100

2

Minimum Turn Speed (platform lowered)

15

1 - 100

2

Minimum Forward Speed (platform elevated)

13

1 - 100

2

Minimum Reverse Speed (platform elevated)

13

1 - 100

2

Minimum Turn Speed (platform elevated)

5

1 - 100

2

Motor Compensation

50 mOhms

0 - 500 mOhms

2

EPPROM Reset

Resets GCM to default factory settings

Notes: (a) MSP Models equipped with stock-picker platform and mid-gate interlock (drive inhibit) switch are factory preset to HIGH.

(b) MSP Models equipped with 12 ft. or 14 ft. lift-limit-switch option are factory preset to HIGH.

Table 4-1. MVL/MSP Ground Control Module - Field Programmable Settings and Factory Preset.

Level-2: Service Level Settings

On LCD Display:

YES =

HIGH =

Level-3: Operator Level Settings

NO =

LOW =

LEVEL

PROGRAMMABLE ITEM

FACTORY PRESET

SETTING RANGE