Chapter 7: application of surge protection devices, Recommendations – ERICO Practical Guide to Electrical Grounding User Manual

Page 124

Advertising
background image

117

Chapter 7: Application Of Surge Protection Devices

Location Category And Exposure Levels As Defined By IEEE STD C62.41-1991

For Line-Line & Line-Neutral

Table 7-1

Location

System

<<Peak

Values (3)>>

1.2/50 µs Volts

Zone (1)Exposure

Volts - kV peak

Current - kA peak,

and 8/20 µs Amps

(2)

1.2/50 µs

0.5 µs-100kHz Ring Wave

-kA pk (4)

A1

Low

2

70

A2

Medium

4

130

A3

High

6

200

B1

Low

2

170

1

B2

Medium

4

330

2

B3

High

6

500

3

C1

Low

6

3

C2

Medium

10

5

C3

High

20

10

Location Category And Exposure Levels As Defined By IEEE STD C62.41-1991

For Neutral-Ground

Table 7-2

Neutral

Distance

System

0.5 µs/100 kHz

1.2/50 x 8/20 µs

Grounding

From

Exposure (3)

Ring Wave Peak

Peak Volt.

Practice (1)

Surge (2)

Voltage - kVp

kVp

Neutral earthed

Close

All

None

None

at service

Nearby

All

1

None

entrance

Far away

All

3

None

Ungrounded

All

Low

2

2

neutral at service

All

Medium

4

4

entrance

All

High

6

6

Note 1. See figure 7-1.
Note 2. See Section 7.3.3 of above standard.
Note 3. Waveshapes are defined in above standard.
Note 4. Combination Wave defined in above standard.

Note 1. Bonding the Neutral to Ground at the service entrance prevents further propagation of Neutral to Ground voltage
and current from sources beyond the service entrance (or any separately derived source). When the Neutral is not bonded to
the earth or the building ground, then Neutral to Ground voltages may be similar to Line to Neutral voltages and Table 7-1
should be consulted.
Note 2. This has not been defined and is a matter of experience and judgment.
Note 3. See section 7.3.3 of above standard.

RECOMMENDATIONS

1. Specify SPDs for the voltage and energy levels as
defined in ANSI/IEEE Std C62.41.

2. Specify SPDs which are UL Listed.

3. SPDs can fail. They usually fail in the short circuit
mode. If this feature is important, decide what to do about
it. For example, fusing the SPD prevents its shorting from
taking out other equipment, but the SPD no longer pro-
vides protection.

4. Is the overall grounding system, to which the SPDs are
connected, the lowest practical impedance?

5. Are connecting leads short, clean and tight?

6. Is the SPD enclosure, if any, suitable for the operating
environment?

Grounding Book 4/14/99 10/5/99 6:02 PM Page 117 (Black plate)

Advertising