31 chapter 2: building lightning protection – ERICO Practical Guide to Electrical Grounding User Manual

Page 39

Advertising
background image

31

Chapter 2: Building Lightning Protection

necting or bonding of the two systems helps to ensure that
there is little possibility of a difference of potential between
the two systems or the two systems’ components.

Because this bonding requirement is difficult to implement
in many facility installations, some low impedance
screened down conductors are being used successfully by
ERICO in Australia and Asia. These conductors are
specially constructed and therefore relatively expensive, but
the reduced chance of side flashes and the ease of
installation are very attractive.

Connectors bond the conductors to the air terminals,

structures, equipment and ground electrodes. They can be
mechanical devices or exothermic welded connections.
Connections to thin metal or to aluminum items must be
mechanical. A properly made connection must last as long
as the planned life of the facility and have:

1.

Adequate mechanical strength to withstand the
forces of nature and any outside force it may
encounter.

2.

High thermal capacity for high current surges.

3.

Low and constant impedance.

4.

Corrosion resistance.

5.

No electrochemical deterioration when joining
different materials.

Grounding electrodes make the connection between the
lightning protection system and the earth. The lightning
electrodes must be bonded to all other grounding system

Plate Electrode

Fig. 2-14

24 Feet Minimum

24" Minimum

12" x 12"
(1 Square Foot)

Shallow Sandy Soil

Fig. 2-13

12 Feet Minimum

12 Inch to 24 Inch
Minimum

Shallow Topsoil

Fig. 2-12

Moist Clay Soil

Fig. 2-11

10' Or More

Grounding Book 4/14/99 10/5/99 6:01 PM Page 31 (Black plate)

Advertising