40 practical guide to electrical grounding – ERICO Practical Guide to Electrical Grounding User Manual

Page 48

Advertising
background image

40

Practical Guide to Electrical Grounding

Fig. 2-38

On large flat roofs or gently sloping roofs, air

terminals are placed in the center area at intervals

not exceeding 50 feet.

Fig. 2-39

Air terminals must be placed within 2 feet of the
corners and edges of flat or gently sloping roofs

and the ends of roof ridges.

Fig. 2-40

Conductor may be welded to air terminal or

attached with an approved clamp.

Fig. 2-41

Dormers on buildings 25’ or less in height require

air terminals on the dormer projecting beyond the

2:1 pitch line require air terminals.

50 Feet Max

50 Feet Max

Over 50 Feet

Place Air Terminal
Anywhere Within
Hatched Area

24" Max

24" Max

2

1

1

2

Protected

Air Terminal
Required

Dormers