Practical Guide to Electrical Grounding

118

Outbuilding

Outbuilding

Xformer

Underground Service

Underground Service

Meter

Meter

Meter

A

B

C

Service
Entrance

Service
Entrance

Service
Entrance

¥ Equipment or outlets and long
branch circuits
¥ All outlets at more than 10m (30 feet)
from Category B
¥ All outlets at more than 20m (60 feet)
from Category C

¥ Feeders and short branch circuits
¥ Distribution panel devices
¥ Bus and feeder industrial plants
¥ Heavy appliance outlets with "short"
connection to service entrance
¥ Lightning systems in large buildings

¥ Outside and service entrance
¥ Service drop from pole to building
¥ Run between meter and panel
¥ Overhead line to detached building
¥ Underground line to well pump

Demarcation between Location Categories B and C is arbitrarily taken to be at the meter or at the main disconnect
(ANSI/NFPA 70-1990, Article 230-70) for low voltage service, or at the secondary of the service transformer if the service is
provided to the user at a higher voltage.

Location Categories For SPD’s

Fig. 7-1

Grounding Book 4/14/99 10/5/99 6:02 PM Page 118 (Black plate)