10. Section 3-19.4: Where the building structural steel

is used as the main conductor of the lightning
protection system, a ground rod or other ground
terminal shall be connected to approximately every
other perimeter steel column. Such connection shall
be made at the base of the column and at intervals
not to exceed an average of about 60 feet.

10" Min

10" Min

10" Min

>1/2 H

>1/2 H

H = Over 24"

H = Over 24"

Air Terminals Height And Supports

Fig. 2-16

Fig. 2-18

No Air Terminal; Roof Edge
Covered Under Higher
Air Terminal Protection.

150 Foot
Radius

20' MAX

25' MAX

24" Or

Higher

Less

Than 24"

Fig. 2-17

Air terminals less than 24” in height are located at

20 feet maximum intervals. If 24 inches or higher,

they can be spaced at 25 feet intervals.

Air terminals located in areas where personnel

may be present, 60 inch terminals are

recommended at mid-roof locations.