55

Chapter 3: Building Interior Bonding & Grounding

Fig. 3-10

Fig. 3-11

Fig. 3-13

Right
Hand
Weld

Left
Hand
Weld

Copper

Left Hand

Right Hand

Weld

Bar Size

Mold Part No.

Mold Part No.

Metal

1/4 x 2”

DFRHEHLH

DFRHEHRH

#250

1/4 x 3

DFFHEKLH

DFFHEKRH

2-#200

1/4 x 4

DFFHEMLH

DFFHEMRH

3-#250

NOTE: The Following Inserts Are Required. They fit
behind the bar and become part of the mold.

Column Type

Insert P/N

Standard Flange

DFSTD

Wide Flange, Parallel Flange

DFWFP

Wide Flange, Tapered Flange

DFWFT

Connector Flush
W/Finished Face
Of Concrete

Nail To Form

3/8"-16, 1/2" Deep, 4 Holes

Plain View

Cadweld Cast Ground
Plate B1642Q

Section AA

4/0 Copper Cable

Stem Fits 1/2" Pipe
For Support And
Positioning

Cadweld RAC2Q2Q #150

A

1/2-13 x 5/8" Silicon
Bronze Bolt W/Washer
2 Required

CADWELD Type GL
2 Hole Lug

Copper Conductor,
Size To Suit

Structural Rebar

CADWELD Connection
Prefab Type RR

Copper Conductor,
Size To Suit (4/0 Max.)

CADWELD Connection,
Type SS To
B162-2Q Ground Plate

2 Hole Ground Plate
CADWELD B162-2Q
Mounted 6" Above
Finished Grade
Alt: B164-2Q 4 Hole
Ground Plate

Concrete Footing

Column

NOTES:
1. Bond Column Rebars To Footer Rebars.
2. Ground Footer Rebars To An External Ground Grid or Rod.
3. Bond Anchor Bolts To Rebars.

Factory Fabrication

Equipment Grounding Pad At Concrete Column

Fig. 3-12

Grounding Book 4/14/99 10/5/99 6:01 PM Page 55 (Black plate)