38 practical guide to electrical grounding – ERICO Practical Guide to Electrical Grounding User Manual

Page 46

Advertising
background image

38

Practical Guide to Electrical Grounding

Fig. 2-28

If a projection extends over 40 feet, a downlead at

(A) must be provided on the projection.

Fig. 2-29

Using the structural steel as the down conductor.

If Over 40 Feet,
Add A Down Lead
At "A"

A

CADWELD
Connection

3/4" Schedule
80 Non-Metallic
Conduit

Concrete Slab

Finished Grade

#2/0

2'-0" Min.

Clearance

1'-0"
Depth

CADWELD
Connection

3/4" x 10'-0"
Driven
Ground Rod

Fig. 2-31

Using the structural steel as the down conductor.

#2/0

CADWELD
Connection

Finished Roof

Fig. 2-32

Detail of conductor through the foundation.

+ 6" To 1'-0"

CADWELD
Type GR
Ground Rod
Connection

5/8" x 10'
Copperclad
Steel
Ground Rod

Below Grade

Bare Copper Conductor

1" PVC Conduit By
Electrical Contractor

Fig. 2-30

Clamp to cast iron or copper water pipe.