Equipment bonding, Chapter 3: building interior bonding & grounding – ERICO Practical Guide to Electrical Grounding User Manual

Page 65

Advertising
background image

57

EQUIPMENT BONDING

Equipment within the facility must be carefully considered
as to its need to be bonded to the facility ground system. Of
course, all electrical equipment must have a grounding
conductor as dictated by the NEC. Additional grounding is
sometimes needed as shown in Figure 3-21. As pointed out
previously, the frequent use of ground plates (Fig. 3-22)
provides accessible grounding points throughout the
building. When removable grounds are required near a
grounded column or beam, a stud can be welded to the
steel and the bonding jumper can be attached using a lug
(Fig. 3-23). Providing mechanical protection to the stud is
recommended.

In cable installations, the tray’s bolted joints do not always
provide the required low resistance. A separate ground
conductor must then be run the length of the tray, bonded to
each tray section and to adjacent steel columns. Or, jumpers
can be used across each joint. The cable can be welded to
the tray if it is steel (Fig. 3-24) or bolted to the tray if it is
aluminum (Fig. 3-25).

Chapter 3: Building Interior Bonding & Grounding

Cable Rack Grounding

Fig. 3-18

Fig. 3-19

1/8 x 3 x 3
Steel, Arc Weld
To Cable Rack Channel

CADWELD VB

CADWELD VN

Alternate -
Specify Right Hand
Or Left Hand

CADWELD Connection
VTC2V Mold
#150 Weld Metal

CADWELD Connection
VTC2V Mold
#150 Weld Metal

CADWELD Connection
PTC2V2V Mold
#250 Weld Metal

Upper Rack

Lower Rack

250 KCMIL Copper

CADWELD
Mold

Ground Plate

Fig. 3-20

Large Motor Grounding Detail

Fig. 3-21

Motor

CADWELD Lug
(2 Hole NEMA)
With Lock Washers
And Bolts

Field To Locate Ground
Plate (2 Hole, CADWELD
CAT. NO. B-162-2Q
Mount Top Flush With
Concrete

CADWELD Type TA

To Ground Loop

4/0 CU GND Cable

Motor

Concrete

Base

Grounding Book 4/14/99 10/5/99 6:01 PM Page 57 (Black plate)

Advertising