Connectors, Practical guide to electrical grounding – ERICO Practical Guide to Electrical Grounding User Manual
Page 94
CONNECTORS
For most connector applications there is a choice of good -
better - best. This choice depends on required life, expected
corrosion, expected level of current (lightning and faults)
and total installed cost. Grounding connections carry little
or no current until a fault occurs. Then, the currents can be
very high and the likelihood of detecting a damaged
connector is low since many of them are concealed. The
result is system degradation or failure. For connectors
hidden behind walls or in the ground, there is no way to
determine if something has degraded. Failure of even one
connection point in a grounding network may be
dangerous, yet go undetected for years.
Connectors are listed in Table 5-2 showing relative cost,
installation time, applicable tests and codes, and
recommendations where they should not, in the author’s
opinion, be used. The final decision is up to the designer!
Practical Guide to Electrical Grounding
Description
Relative
Installation
Codes
Not
Cost
Time
Tests
to use
Split Bolt
LOW
MEDIUM
UL
Hidden
Service Posts LOW
MEDIUM
UL
Hidden
Pipe Clamp
MEDIUM
UL
Hidden
Compression
MEDIUM
MEDIUM
UL
Devices
TO HIGH TO HIGH
Ground Rod
VERY
MEDIUM
UL
Clamps
LOW
Brazed
LOW
HIGH
Connection
CADWELD
MEDIUM
MEDIUM
IEEE Std 80,
Connection
TO HIGH TO HIGH
IEEE Std 837
and UL
86
R
CADWELD
R
R
CADWELD
+ CADWELD =
Screw
Coupler
Fig. 5-6
Fig. 5-7
Braze
Connectors
Table 5-2
Grounding Book 4/14/99 10/5/99 6:02 PM Page 86 (Black plate)