Practical Guide to Electrical Grounding

54

Fig. 3-8

Fig. 3-9

.

.

.

.

.

.

.

..

.

.

.

.

.

. .

.

.

.

. .

.

.

.

.

.

.

.

.

.

. .

.

. . .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

. . ..

.

.

.

.

.

. . . . .

.

.

.
.

.

.

.

.

.

.

.

.

. .

.

.

.

.

. .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

Masonary Anchors
For Mounting Bolts

ERICO Insulator and Mounting Bracket
(Includes Insulator Mounting Bolts
And Assembly Washers)

Copper Bus Along Wall

CADWELD Type LJ Connection -
Cable To Bus

Insulated Or Bare Copper
Conductor To Below Floor
Ground Grid

Insulated Or Bare Copper

Conductor To Ground Grid Via
1" Dia. PVC Sleeve In Floor Slab

Copper Ground Conductor

CADWELD
Type GR or GT

Ground Rod

Beyond Roof
Drip Line,
18" Minimum

Underfloor Ground Grid Detail

1" PVC Sleeve Thru Wall
Slope @ 1/4" Per Foot

Ground Grid #6 AWG Solid Copper
Conductor @ 24" x 48" Centers.
Use CADWELD Connections
At Each Intersection Or Use
ERICO Prefabricated Wire Mesh
On 24" x 48 " Centers

Min. 12" From Wall Around Entire
Perimeter Of Building

CADWELD PT Connection To Grid

Interior Floor Slab

Steel
Angle Or
Column

CADWELD
Connection

Copper Bar

Minimum

Copper

Mold

Weld

Width Of

Bar Size

Part No.

Metal

Steel

1/8 x 1

DFCCE*

#115

3”

1/4 x 1

DFCEE*

150

3”

1/4 x 2

DFFEH*

2-200

4”

1/4 x 3

DFFEK*

500

4”

1/4 x 4

DFFEM*

3-250

4”

*Add RH or LH for right or left hand right hand shown.

Grounding Book 4/14/99 10/5/99 6:01 PM Page 54 (Black plate)