Appendix

Output Wiring: PLC Relays are mapped to output events in the SQC-222 Systems
Setup, PLC Relays menu. SQC-222 Relays 1 to 8 correspond to Omron PLC relays
10.00 to 10.07.

Omron PLC output wiring is illustrated above. Notice that some relays (i.e. 02/03 and
04/05/06/07 share a common terminal).

Note: The internal 24VDC, .3A supply of the Omron PLC is NOT adequate to serve as
the supply shown in the diagram above.