INFICON Cygnus Editor Software Manual User Manual

Page 50

Advertising
background image

3 - 12

IP

N 07

4-

39

4-

P1

A

Cygnus Editor Operating Manual

Figure 3-13 Entering an Input Name

Figure 3-14 Accepting an Input Name

Output Types can also be assigned on this page. Each output can be configured
as:

Normally Open . . . . . . . . . . . . . . . . which means the relay is held open by the

controller, during periods of inactivity, and
then closed to indicate activity or provide a
signal.

Normally Closed . . . . . . . . . . . . . . . which means the relay is held closed by the

controller, during periods of inactivity, and
then opened to indicate activity or provide a
signal.

Configuring an Output to be Normally Open or Normally Closed is largely
determined by the state required, at the input receiving this signal, to start or stop
a device or process. Some Outputs are configured by the system based on
parameter settings made in the Hardware Parameters, as shown in the example of

Figure 3-11

.

If a Controller is attached to the PC then the Input and Output names from the
controller can be read and displayed in the Input/Output Names page of the Editor.
If all parameters were queried from the Main Page then the names will be shown
on the Input/Output Names page when the page is opened. Any name assigned by
the system will be shown with a grey background and will be protected against
editing (see

Figure 3-15

). Otherwise, when the page is opened the names can be

read from the controller by pressing the Query All button on the Input/Output

Advertising