Terminal assignment – Lenze E94AZPS User Manual

Page 40

Advertising
background image

Electrical installation

Wiring
Terminal assignment

4

l

40

EDK94ZPS113 DE/EN/FR/ES/IT 4.0

4.3.3

Terminal assignment

I

Tip!

Complete the wiring of the installation backplane before plugging
in the standard device. The upper terminals of the installation
backplane cannot be connected with a plugged−in standard device.

IT system

(

Stop!

Overvoltage on components:
On IT systems an earth fault in the installation can cause
impermissible overvoltages.
Possible consequences:
Destruction of the device.
Protective measures:
If the devices are operated on IT systems, the internal connection of
the filters to the protective earth in the installation backplane has
to be disconnected.