Electrical installation – Lenze E94AZPS User Manual
Page 45

Electrical installation
Wiring
Terminal assignment
l
45
EDK94ZPS113 DE/EN/FR/ES/IT 4.0
Motor temperature monitoring
Terminal X106
Labelling
Description
T1
T2
Motor temperature monitoring with PTC element
(type−A sensor, switching performance according to
EN 60947−8 for type−A tripping units) or thermostat
(NC contact).
SSP940X106
Terminal data
Max. conductor cross−section
Tightening torque
!
[mm
2
]
[AWG]
[Nm]
[lb−in]
Flexible
2.5
12
0.5 ... 0.6
4.5 ... 5.3
PZ0
With wire end
ferrule
Motor brake control (optional)
,
Observe the notes in the Mounting Instructions on the motor brake
control.
Terminal X107
Labelling
Description
Connection of the motor holding brake
BD1
BD2
+ (Lenze: WH)
− (Lenze: BN)
E94AZHX0051: 24 V DC, max. 2.5 A
Observe correct polarity!
+ / −
Supply voltage for the motor holding brake
(18 ... 30 V DC)
Observe correct polarity!
SSP940X107
Terminal data
Max. conductor cross−section
Tightening torque
!
[mm
2
]
[AWG]
[Nm]
[lb−in]
Flexible
2.5
12
0.5 ... 0.6
4.5 ... 5.3
PZ0
With wire end