Informazioni sulla sicurezza – Lenze E94AZPS User Manual

Page 97

Advertising
background image

Informazioni sulla sicurezza

Informazioni sulla sicurezza per l’installazione secondo UL o UR

1

l

97

EDK94ZPS113 DE/EN/FR/ES/IT 4.0

1.2

Informazioni sulla sicurezza per l’installazione secondo U

L

o U

R

J

Warnings!

ƒ

Branch circuit protection:
Suitable for use on a circuit capable of delivering not more than
5000 rms symmetrical amperes, 500 V max.

ƒ

Voltage of the fuses must at least be suitable with the input
voltage of the drive.

ƒ

The integral solid state protection does not provide branch circuit
protection and that branch circuit protection has to be provided
externally in accordance with manufacturers instructions, the
National Electrical Code and any additional codes.

ƒ

For information on the protection level of the internal overload
protection for a motor load, see the corresponding Application
Manuals or Software Helps.

ƒ

For information on rating and proper connection of the thermal
protector (only for connection to motors having integral thermal
protection), see the corresponding Application Manuals or
Software Helps.

ƒ

Maximum surrounding air temperature: 55 °C.

ƒ

Use 60/75 °C copper wire only, except for control circuits.

Advertising