Cable specification, 6electrical installation – Lenze EMF2179IB User Manual

Page 58

Advertising
background image

6

Electrical installation

Cable specification

EDKMF2179 DE/EN/FR 4.0

58

l

H2 Kabelspezifikation−Thincable

Cable specification

The nodes on the bus system have to be wired with a fieldbus cable (DeviceNet thick or thin
cable) complying with the DeviceNet specification (DeviceNet Adaption of CIP, Edition 1.1,
Volume Three).

Manufacturers of DeviceNet thick and thin cables for example are Belden Inc., Lapp Group,
C&M Corp., and Madison Cable Corp.

Properties of the "Thick Cable" in accordance with DeviceNet specification

General features

Structure

Two shielded balanced lines, common axis with drain wire in the
centre

Total shielding

65% coverage
AWG 36 (at least 0.12 mm) of tin−coated copper braid (individually
tinned)

Drain wire

At least copper 18; at least 19 cores (individually tinned)

Outer diameter

10.41 ... 12.45 mm

Concentricity

The radius deviation has to be within 15 % of half the outside
diameter.

Cable sheath labelling

Name of vendor, part no., and additional labelling

Spec. DC resistance (braid, wrapping, leakage)

5.74

W

/km (nom. up to 20 °C)

Certifications (U.S. and Canada)

NEC (UL), CL2/CL3 (min.)

Bend radius

20 x diameter (installation) / 7 x diameter (fixed)

Ambient temperature (operation)

−20 ... +60 °C at 8 amperes;
linear current derating to zero at 80 °C

Storage temperature

−40 ... +85 °C

Pull tension

845.5 N

max