6electrical installation – Lenze EMF2179IB User Manual

Page 60

Advertising
background image

6

Electrical installation

Cable specification

EDKMF2179 DE/EN/FR 4.0

60

l

H2 Kabelspezifikation−Thincable

Properties of the "Thin Cable" in accordance with DeviceNet specification

General features

Structure

Two shielded balanced lines, common axis with drain wire in the
centre

Total shielding

65% coverage
AWG 36 (at least 0.12 mm) of tin−coated copper braid (individually
tinned)

Drain wire

At least copper 22; at least 19 cores (individually tinned)

Outer diameter

6.096 ... 7.112 mm

Concentricity

The radius deviation has to be within 20 % of half the outside
diameter.

Cable sheath labelling

Name of vendor, part no., and additional labelling

Spec. DC resistance (braid, wrapping, leakage)

10.5

W

/km (nom. at 20 °C)

Certifications (U.S. and Canada)

NEC (UL), CL2 (min.)

Bend radius

20 x diameter (installation) / 7 x diameter (fixed)

Ambient temperature (operation)

−20 ... +70 °C at 1.5 amperes;
linear current derating to zero at 80 °C

Storage temperature

−40 ... +85°C

Pull tension

289.23 N

max

Features of the data line

Insulation diameter

1.96 mm (nom.)

Conductor pair

At least copper 24; at least 19 cores (individually tinned)

Colours

Light blue, white

Pair windings / m

Approx. 16

Shielding/conductor pair

1000/1000, Al/Mylar, Al side on the outside, with w/shorting fold (for
tensile load)

Impedance

120

W

+/− 10 % at 1 MHz

Runtime

4.46 ns/m (max.)

Capacitance between conductors

39.37 pF/m at 1 kHz (nom.)

Capacitance between one conductor and
another which is connected to the shield.

78.74 pF/m at 1 kHz (nom.)

Capacitive assymetry

3.94 pF/km at 1 kHz (max.)

Spec. DC resistance at 20 °C

91.86

W

/km (max.)

Damping

0.95 dB/100 m at 125 kHz (max.)
1.64 dB/100 m at 500 kHz (max.)
2.30 dB/100 m at 1.00 MHz (max.)

Advertising