On off, Commissioning, Address bd – Lenze EMF2179IB User Manual
Page 67
Advertising
![background image](/manuals/565925/67/background.png)
Commissioning
Possible settings via DIP switch
EDKMF2179 DE/EN/FR 4.0
67
l
H1inbet−DeN−uebrate
Setting of the device address
OPEN
ON
OFF
Address
Bd
1 2
4
3
5 6 7 8 9 10
Fig. 3
Address assignment via DIP switch
ƒ The device addresses for several interconnected DeviceNet nodes have to differ from
each other.
ƒ The sum of the valencies of all switches in the ON position (1 ... 6) produces the
desired node address.
DIP switches
Value
Example
Switch position
Device address
1
32
OFF
16 + 4 + 2 + 1 = 23
2
16
ON
3
8
OFF
4
4
ON
5
2
ON
6
1
ON