Commissioning – Lenze EMF2179IB User Manual
Page 73
Commissioning
Enabling the standard device via the communication module
EDKMF2179 DE/EN/FR 4.0
73
l
H2_FirstOn−unkontroll_Anlauf
Enabling ECSXX via the communication module
Step
Procedure
Comments
1.
Select "AIF" control
interface via code.
See documentation for the corresponding ECS controller.
Example of the first commissioning with signal configuration
"1013":
Write (C0005 = 1013)
l
Class: 0x6E (110
dec
)
l
Instance: 0x5
l
Attribute: 1
l
Service code: Set Single Attribute
l
Data send: 0x9A9250 (10130000
dec
)
2.
Set C0142 = 0
See "Protection against uncontrolled restart" (
^ 74).
3.
Set terminals X6/SI1
and X6/SI2 to HIGH
level
Terminals X6/SI1 (controller enable/inhibit) and X6/SI2 (pulse
enable/inhibit) are always active and have to be on HIGH level
during DeviceNet operation. Otherwise the controller cannot be
enabled via DeviceNet.
4.
The controller now accepts parameter and process data.