2 electrical data, Electrical data, Technical data – Lenze EPM-H510 User Manual

Page 47

Advertising
background image

Technical data

L

47

EDBEPM-H510 DE/EN/FR 4.0

2.2

Electrical data

Field

Values

Display

Type

LCD monochrom STN, 5.5 “

Display

Display format

graphical

Touch screen

Matrix 20 8 (12 16 pixel)

Resolution

240 x 128 pixel

Visible size

123.0 x 68.0 mm

Lines Characters

100 %
200 %
400 %

16 x 40
8 x 20
4 x 10

Character size

100 %
200 %
400 %

3 x 4 mm, text: 6 x 8 pixel
6 x 8 mm, text: 12 x 16 pixel
12 x 16 mm, text: 24 x 32 pixel

Fonts

programmable

Contrast setting

via touch screen

Background light

Service life at 25 °C

CCFL tube
15000 h

Electrical connection DC voltage supply

+18 ... 32 VDC

Electrical connection

Power consumption

15 W at 24 VDC

Fusing

Miniature fuse

5 20 mm, 800 mA / F

Network:
System bus (CAN)

Protocol

Lenze System bus (CAN)

System bus (CAN)

Communication medium

DIN ISO 11898

Network topology

Line (terminated at both ends with 120

)

System bus participants

Master or slave

Max. number of participants

63

Baud rate [kBit/s]

20

50

125

250

500

1000

Max. bus length [m]

2500

1000

500

250

80

25

Memory

User program

512 kB

Memory

Data memory
(energy-dependent, can only be

used with an internal buffer

battery)

128 kB

Interfaces

Serial

Interfaces

MSP (DB25 socket) RS232

Battery

Saving of internal data and

real-time clock with data

Lithium battery 3 V,

19 mm

Show/Hide Bookmarks

Advertising