Commissioning

Before switching on

7

EDK71MMXXX−020 DE/EN/FR 5.0

101

L

−26−

(

Stop!

Short circuits or earth faults in the wiring destroy the starttec. Check the
wiring for short circuit and earth fault.

To avoid personal injuries or property damages, check

l

the wiring for completeness, short circuit and earth fault.

l

the "EMERGENCY OFF" function of the complete system.

l

whether the rated motor current is correctly set.

)

Note!

Testing mode without motor

If no motor is connected to the starttec and the starttec is enabled
(X3/28 = HIGH), the mains phase failure detection and the I

2

xt monitoring

respond due to the nature of the system.

To prevent the drive from being switched off with an error message, adjust
the mains phase failure detection and the I

2

xt monitoring to "warning"

during the testing mode (C0122 = 1, C0123 = 1).

(

Stop!

The starttec is designed for motor powers 250 W ... 4 kW or motor currents
1 A ... 9.5 A.

The following must be observed if you operate motors with powers
< 250 W or motor currents < 1 A in the operating mode "Reversal":

The operating mode is not detected automatically due to the low motor
current.

It is vital to set the operating mode "Reversal" manually with C0015 =
2. Otherwise, the starttec may be destroyed!