Commissioning, Code table – Lenze EDK71MMXXX−020 User Manual

Page 125

Advertising
background image

Commissioning

Code table

7

EDK71MMXXX−020 DE/EN/FR 5.0

125

L

Code

IMPORTANT

Setting options

No.

Selection

Lenze

Designation

C0357

v

System bus
monitoring time

1 CAN−IN1 (sync)

0

0
= monitoring
inactive

{1 ms}

65000 Active if C0360 = 1

TRIP CE1 with
communication fault

2 CAN−IN2

0

TRIP CE2 with
communication fault

3 CAN−IN1 (time)

0

Active if C0360 = 0
TRIP CE3 with
communication fault

C0358

v

Reset node

0

0

Without function

Configure system bus reset
nodal point

1

System bus reset

C0359

v

System bus
status

0

Operational

Display only

1

Preoperational

2

Warning

3

Bus Off

C0360

v

Control of
process data
channel CAN1

1

0

Event or time control

1

Sync control

C0370

v

Activate remote
parameter
setting

0

Deactivated

Can only be read with bus
function modules on FIF

1 ...
63

Activates respective CAN address

1 = CAN address 1
63 = CAN address 63

255

No system bus (CAN) available

Display only

C0372

Identification of
function module

0

No function module

Display only

2

System bus (CAN)

6

Other bus function module on FIF,
e.g. INTERBUS, PROFIBUS−DP, ...

10

No valid identification