Electrical installation

Connection of AS interface

5

EDK71MMXXX−020 DE/EN/FR 5.0

95

L

)

Note!

The AS interface is only active with starttec type E71MM402FxAxxx!

−24−

)

Note!

If the mains voltage is switched on and no supply voltage DC 24 V is
applied, the AS−i status bits have the value TRUE. This may cause the status
messages to be misanalysed (e. g. "ready for operation").

Remedy:

l

Monitor the incoming cable of the supply voltage DC 24 V for wire
breakage. The wire breakage monitoring must be integrated into the
safety chain of the machine/system.

or

l

Assign an AS−i status bit with the signal "TRIP":

C0415/5 = 25 or C0415/6 = 25

Then, "TRIP" is also signalling, when the supply voltage DC 24 V is not
applied anymore.

Communications data

Protocol / communication medium

AS−I

Network topology

Tree

Node

Slave

Slave profile

S−7.F (IO code: 7

hex

, ID code: F

hex

)

Operating parameters

F

hex

Data structure

3 AS−I data bits (D0, D1, D2) to starttec
2 AS−I data bits (D0, D1) from starttec

Max. number of nodes

31

Transfer rate [kbit/s]

167

Cycle time [ms]

5 ms (with 31 nodes)

Max. bus length [m]

100