Electrical installation, Reversal of direction of rotation – Lenze EDK71MMXXX−020 User Manual

Page 91

Advertising
background image

Electrical installation

Reversal of direction of rotation

5

EDK71MMXXX−020 DE/EN/FR 5.0

91

L

Terminal

Data

Function (bold = Lenze setting)

X3/59

Supply voltage connection +24 VDC
Reference: X3/7

+18 VDC − 0 % ... +30 VDC + 0 %)
Min. 200 mA
Max. 1.5 A (all inputs and outputs
are connected)

X3/20

DC voltage output + 24 VDC
Reference: X3/7

+18 VDC ... +30 VDC
Max. 500 mA

X3/7

Reference potential

Digital inputs

X3/28

Release/inhibit starttec

HIGH

starttec released

LOW (0 V ... +3 V)
HIGH (+12 V ... +30 V)
R

i

= > 4 k

W

Function in C0410 is freely
assignable

LOW

starttec inhibited

X3/E1

Start motor

HIGH

Start motor

LOW

Stop motor

X3/E2

Direction of rotation

HIGH

Counter−clockwise
rotation (CCW)

LOW

Clockwise rotation
(CW)

X3/E3

Brake control

HIGH

Release brake

LOW

Apply brake

X3/E4

Not assigned

X3/E5

Digital outputs

X3/A1

Status of motor

HIGH

Motor is running

LOW (0 V ... +3 V)
HIGH (+12 V ... +30 V)
Max. 200 mA per output
Function in C0415 is freely
assignable

LOW

Motor is stopped

X3/A2

Status of direction of
rotation

HIGH

Counter−clockwise
rotation (CCW)

LOW

Clockwise rotation
(CW)

X3/A3

Status of brake

HIGH

Brake is released

LOW

Brake is applied

X3/A4

Not assigned

Motor temperature monitoring

X3/T1

Motor temperature monitoring connection with thermal
contact (NC contact)

l

Remove bridge between X3/T1
and X3/T2

l

Route supply cable to X3/T1
and X3/T2 separately

X3/T2

AS interface

X3/A+

AS interface connection

Only active for E71MM402FxAxxx
^ 95

X3/A−

Advertising