RKI Instruments GasWatch 2 Manual User Manual

Page 18

Advertising
background image

13 • Operation

GasWatch 2 Operator’s Manual

Alarms

This section covers alarm indications. It also tells you how to reset the
GasWatch 2 after an alarm has occurred and how to respond to an alarm
condition.

Alarm Indications, GW-2C & GW-2H

The GW-2C and the GW-2H will sound an alarm and the unit will vibrate
when the target gas concentration, CO or H

2

S, rises above the low alarm

point. The GasWatch 2 also sounds an alarm and vibrates when the high
alarm point, the STEL alarm point, or the TWA alarm point is reached. It
also has a low battery warning, a dead battery alarm, an over range alarm,
a sensor failure alarm, and a system failure alarm. See Table 3 below for a
description of each alarm indication.

Alarm Indications, GW-2X

The GW-2X will sound an alarm and the unit will vibrate when the oxygen
concentration falls below the low alarm point or rises above the high alarm
point. It also has a low battery warning, a dead battery alarm, an over
range alarm, a sensor failure alarm, and a system failure alarm. See
Table 3 below for a description of each alarm indication.

The table below summarizes the types of alarms produced by the
GasWatch 2.

Table 3: Alarm Types and Indications

Alarm Type

LCD Indications

Other Indications

Low Alarm

Concentration of gas
rises above the low
alarm point, or for the
GW-2X, falls below
the low alarm point.

• Gas reading

flashes.

• Back light turns on.

• Pulsing tone once

per second.

• Unit vibrates once

per second.

• Alarm lights flash

once per second.

High Alarm

Concentration of gas
rises above the high
alarm point.

• Gas reading

flashes.

• Back light turns on.

• Pulsing tone twice

per second.

• Unit vibrates twice

per second.

• Alarm light flashes

twice per second.

Advertising