Chapter 2 installation 16 – SATEC C191HM User Manual

Page 25

Advertising
background image

Chapter 2 Installation

16

9-PIN DB9 FEMALE CONNECTOR

POWERMETER

14

15

13

RS-232

RTS

CTS

8

7

RxD

TxD

SG

TxD

DTR

DSR

6

4

3

RxD

GND

5

2

c99-11015

IBM PC/COMPATIBLE

Figure 2-15 RS-232 Simple 3-Wire Computer Connection, 9-pin

Figure 2-16 RS-485 Multi-drop Computer Connection

NOTE:

Where an RS-232/RS-485 converter is used on a computer connection, R1 is not

applicable since it is built in to the converter.

Activity on the communications port lines is indicated via the TXD and RXD
LEDs, on the front panel and via the Status Information menu (see Chapter 6).
A full description of the communication protocols may be found in the C191HM
ASCII, Modbus and DNP3.0 Communications Manuals
provided with your

c99-09035

+

+

+

-

-

-

C192PF8 POWER FACTOR CONTROLLERS

IBM PC /COMPATIBLE
or RS-2 32/RS-485 CONVERTER

RS-485

RxD

R1

#1

13

13

13

15

15

15

14

14

14

#2

R2

#32

TxD

TxD-

RxD-

Shi eld

Sh ield

R1, R2 = 200-500 Ohm,

0.5W

Shield

Advertising