Appendix: Technical Specifications

49

Appendix: Technical Specifications

7. ions

Input and Output Ratings

3 galvanically
isolated voltage
inputs

690 V:
(standard)

DIRECT INPUT (690V line-to-line voltage and 400V line-
to-neutral) Burden: <0.5 VA
INPUT USING PT Burden: <0.15 VA

120

V:

(optional)

INPUT USING PT (120V line-to-line voltage)
Burden: <0.1 VA

3 galvanically
isolated current
inputs

5 A:
(standard)

INPUT VIA CT with 5A secondary output Burden: <0.1
VA
Overload withstand: 10A RMS continuous, 250A RMS for
1 second

1 A:
(optional)

INPUT VIA CT with 1A secondary output Burden: <0.02
VA
Overload withstand: 2A RMS continuous, 50A RMS for 1
second

Voltage and current input
terminals

UL recognized Screws: Brass, M4
Maximum wire section: 2.5 mm

2

(12 AWG)

Optically isolated
communication port

EIA RS-485 or RS-232 standard (factory set)
Maximum wire section: 1.5 mm

2

(14 AWG)

Relay outputs

5 relays rated at 5A, 250 V AC / 5A, 30 V DC /

0.5A, 110 V DC 2 contacts (SPST Form A)

1 relay rated at 5A, 250 V AC / 5A, 30 V DC /

0.5A, 110 V DC 3 contacts (SPDT Form C)

2 relays rated at 3A, 250 V AC / 3A, 30 V DC /

0.5A, 110 V DC 2 contacts (SPST Form A)

Maximum wire section: 1.5 mm

2

(16 AWG)

Analog output (optional)

4-20 mA
0-20 mA

Accuracy 0.5%, Non-linearity 0.2%

Load up to 510 Ohm
24V DC external power supply required

Status input

Dry contact for external synchronization or monitoring

Display

3 windows high-brightness seven-segment digit LEDs
3 color LED bar graph 40-110%

Power Supply

Galvanically isolated power
supply (factory set)
120&230V AC / 120&220 V DC
12 V DC
24 V DC
48 V DC



85 - 265V AC 50/60 Hz and 88- 290V DC 10 W
9.6 - 19 V DC
19 - 37 V DC
37 - 72 V DC